The power limit value can be set from the panel, from 80% to 110% freely.
● When the active power (KW) reaches 95% of the set value, the indicator will display; when the active power (KW) reaches 100% of the set value, 0VDC is output to ensure that the drive system cannot continue to load.
● When the total current (Itotal) reaches 95% of the set value, the indicator will display; when the total current (Itotal) reaches 100% of the set value, output 0VDC to ensure that the drive system cannot continue to be loaded.
● When the frequency is lower than 48HZ, the indicator light will display and output 0VDC to ensure that the transmission system cannot continue to be loaded.
● When the rate of load mutation exceeds the inherent characteristics of the diesel engine, delay the load loading
To ensure the stable operation of diesel generator sets.
The main equipment in the diesel generator set control system is all in the control cabinet (GEN).